Tyco TY3451 Sprinkler Head ( 3/4” OD 1/2" NPT ) 200F 93C Sidewall WU/P
Looking to guard your building against fire incidents? Tyco® Series TY-B sprinklers are designed for use in commercial occupancies such as banks, hotels, malls, factories, refineries, and chemical plants. When it comes to fire safety, preparation is everything. These sprinklers discharge a hemispherical water spray pattern in the area beneath the sprinkler using a small frame and narrow profile bulb.
Tyco TY3451 Sprinkler Head ( 3/4” OD ) 1/2 NPT 200F 93C BRASS Sidewall WU/P NEW USA $19
TYCO Standard Spray Standard Response TY-B Vertical Sidewall, K=5.6, 1/2 NPT (SIN TY3451), 200F/93C, Brass
- Approvals: UL, C-UL, FM, LPCB & NYC
- Maximum Working Pressure: 175 psi (12,1 bar)
- Discharge Coefficient: K = 5.6 GPM/psi½ (80,6 LPM/bar½)
- Sprinkler joint 1/2 in. NPT (DN15)
- Finishes: natural brass, pure white (RAL9010) polyester, signal white (RAL9003) polyester, jet black (RAL9005) polyester, chrome plated, wax coated 286°F (141°C) max, lead coated, wax-over-coated 286°F (141°C) max
- Temperature Ratings:
+ 135°F (57°C) bulb liquid color orange
+ 155°F (68°C) bulb liquid color red
+ 175°F (79°C) bulb liquid color yellow
+ 200°F (93°C bulb liquid color green
+ 286°F (141°C) bulb liquid color blue
+ 360°F (182°C) bulb liquid color mauve
- It is designed for installation along a wall or the side of a beam and just beneath a smooth ceiling. Sidewall sprinklers are commonly used instead of pendent or upright sprinklers due to aesthetics or building construction considerations, where piping across the ceiling is not desirable.
- Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres.